BBI 12-VOLT MODULE SYSTEMS
510 A/H - 1360 A/H  @ 20 HRS.
2V CELLS

BBI  12-VOLT  SBY SYSTEMS SPECIFICATIONS

12 VOLT SYSTEMS MODEL # DIMENSIONS RATED A/H (6 Hrs) RATED A/H (20 Hrs) USABLE A/H (20 Hrs) RATED Watts/Hr (20 Hrs) USABLE Watts/Hr (20 Hrs) CHARGE RATE Min/Max Amps Weight Lbs. Short Circuit Ratings in Amps/ 104'F
6-SBY85-13
41 x 7.00 x 25/34
510 637 509 8179 6543 45 - 105 Amps 94 7,200
6-SBY85-15
41 x 7.75 x 25/34
595 743 594 9540 7632 55 -125 Amps 107 8,400
6-SBY85-17
41 x 8.50 x 25/34
680 850 680 10,914 8,731 68 - 136 Amps 119 9,600
6-SBY85-19
41 x 9.50 x 25/34
765 956 764 12,275 9,820 76.5 - 153 Amps 130 10,800
6-SBY85-21
41 x 10.00 x 25/34
850 1062 849 13,636 10,908 85 - 170 Amps 142 12,000
6-SBY85-23
41 x 11.50 x 25/34
935 1168 934 14,997 11,997 93.5 - 187 Amps 152 13,300
6-SBY85-25
41 x 11.50 x 25/34
1020 1275 1020 16,371 13,096 102 - 204 Amps 166 14,400
6-SBY85-27
41 x 12.25 x 25/34
1105 1381 1104 17,732 14,185 110.5 - 221 Amps 180 15,600
6-SBY85-29
41 x 13.00 x 25/34
1190 1487 1189 19,093 15,274 120 - 240 Amps 194 16,800
6-SBY85-31
41 x 13.75 x 25/34
1275 1593 1274 20,454 16,363 127.5 - 255 Amps 210 18,000
6-SBY85-33
41 x 14.50 x 25/34
1360 1700 1360 21,828 17,462 136 - 272 Amps 224 19,200

** 85 amp plate batteries, 25” height including cover 